Heat Resisting(Flame retardant) Power Cable
1.Scope ofapplication
It is used as power transmission cable for electric equipmentsof rated voltage 0.6/1kV or lower in bad environment or thatwith high temperature.
2.Executive standard
Enterprise standard
TICW/03-2009
3.Performance in Usage
1: Rated voltage Uo/U: 0.6/1kV
2: Max.working temperature allowed by cable is 200C forcable with fluoroplastic insulation and sheath,105C for cablewith fluoroplastic insulation, 105C heat resistanc and PVCsheath, and 180C for cable with fluo- roplastic insulation andsilicon rubber sheath.
3: Max temperature of cable conductor is no more than 250Cduring short circuit (The longest lasting time is no more than 5s).
4: Temperature for installation is no less than -15C.5: Bending radius of cable as followsIt is no less than 20 times that of cable outer diam- eter forcable with single core It is no less than 15 times that of cableouter diameter for cable with 3 cores6: Power cable with fluoroplastic insulation and sheath hasgood features of chemical corrosion resis- tance hightemperature resistance and flame retardance.
4. Type and Description
Type and Description in Table 1
Table 1

Note: 22 means steel tape armor “22" should be changed into “32” for cable with steel wire armor (if needed).
5.Specification of Cable
“core number * nominal cross section” stands forcable specification. Please see the following table 2 forcore number and nominalcross section
Table 2

6.Technical Parameter
1: DC resistance of conductor at 20C shall meet therequirement of GB/T3956 standard.
2: Cable shall bear AC voltage test of 3500V for 5minwithout puncture of insulation.