Product Center

current position: Home > Product Center > Control cable
Flame Retardant Control Cable

Flame Retardant Control Cable

  • Category:Control cable
  • Browse number:
  • QR code:
  • Release time:2023-08-14 18:02:18
  • Product description

Flame Retardant Control Cable


1.Application

Applicable to the control system,controlloop andprotection cricuit(which request flame-retardant)with the rated voltage 450/750V(orlower)


2.mplementation ofstandards

GB/T9330.2.3-2008

GB/T19666-2005(equaltolEC60331,60332)


3.Using characteristics

1.The max working temperature of conductor(of a cable)is 70C(PVCinsulated): 90C(XLPEinsulated).

2.The ambient temperature forlayingiS notlowerthan 0C .

3.The least allowed bending radius steeltape-armoredcable is 6 times the outer diameter ofthe cable:6 times the outer diameter of the cable(the screensoft cable); steel tape-armored or cu tape armoredshield calble is 12 times the outer diameter ofthe cable


4. Type and Denomination

Type

 Denomination
ZA(B、C、D)KVV


PVC insulated and sheathed flame-retardant A(B.C.D)control cable

ZA(B、C、D)KVVP


PVC insulated and sheathed braid shield flame-retardant A(B.C.D)control cable

ZA(B、C、D)KVVP2


PVC insulated and sheathed Cu tape armored shield flame-retardant A(B.C.D)control cable

ZA(B、C、D)KVVP3


PVC insulated and sheathed aluminum tape armored shield flame-retardant A(B.C.D)control cable

ZA(B、C、D)KVV22


PVC insulated and sheathed steel tape armored flame-retardant A(B.C.D)control cable

ZA(B、C、D)KVVP2-22


PVC insulated and sheathed Cu tape armored shield control steel tape armored flame-retardantA(B.C.D)control cable

ZA(B、C、DKVV32


PVC insulated and sheathed steel wire braid flame-retardant A(B.C.D)control cable

ZA(B、C、D)KVVR


PVC insulated and sheathed flame-retardant A(B.C.D) soft control cable

ZA(B、C、D)KVVRP


PVC insulated and sheathed braid shielded flame-retardant A(B.C.D) soft control cable

ZA(B、C、D)KYJV


XLPE insulated PVC sheathed flame-retardent A(B.C.D)control cable

ZA(B、C、D)KYJVP


XLPE insulated PVC sheathed b raid shield flame-retardent A(B、C、D)control cable

ZA(B、C、D)-KYJVP2


XLPE insulated PVC sheathed Cu tape armored shield flame-retardent A(B.C.D)control cable

ZA(B、C、D)KYJVP3


XLPE insulated PVC sheathed aluminum tape armored shield flame-retardent A(B.C.D)control cable

ZA(B、C、DKYJV22


XLPE insulated PVC sheathed steel tape armored flame-retardent A(B.C.D)control cable

ZA(B、C、D)-KYJVP2-22


XLPE insulated PVC sheathed Cu tape armored shield control steel tape armored A(B.C.D)control cable

ZA(B、C、D)KYJV32


XLPE insulated PVC sheathed steel wire braid A(B.CD)control cable


5.Specification range


Typ

 Nominal cross section area mm2
0.751.01.52.54610

 Core NO.

ZA(B,C,D)-KVV

ZA(B,C,D)-KVVP

ZA(B,C,D)-KYJV

ZA(B,C,D)-KYJVP

2-612-142-10

ZA(B,C,D)-KVVP2

ZA(B,C,D)-KVVP3

ZA(B,C,D)-KYJVP2

ZA(B,C,D)-KYJVP3

4-614-144-10

ZA(B,C,D)-KVV22

ZA(B,C,D)-KVVP2-22

ZA(B,C,D)-KYJV22

ZA(B,C,D)-KYJVP2-22

7-614-614-144-10

ZA(B,C,D)-KVV32

ZA(B,C,D)-KVJV32

7-614-614-14
4-10
ZA(B,C,D)-KVVR2-614-144-10
ZA(B,C,D)-KVVRP2-61
4-144-10


6.Technolgicalparameters


No


Project


Unit


Index


Test method

1


Cable structure and conductor resistance

GB/T3956-2008(IEC60228:2004)

Complies with the standard ofGB/T3956-2008(IEC60228:2004)

GB/T3048.4-2007

2


Spark test(AC.Voltage 50Hz)

KV6GB/T3048.9-2007
3


Frequency(5min)voltage test

KV3GB/T3048.8-2007
4


Insulation voltage test

0.6mm≤0.6mm

0.6mm=0.6mm

KV

2

2.5

GB/T3048.8-2007


2.Flame-retardant

A Single-core flame-retardant

Code


Specimen diameter(mm)


For fire time index(S)


Complianceindex


Test method

Z

D≤25

60

Specimen char is far from fixture50mm-540mm

GB/T18380.1-2001

(IEC60332-1:1993)

GB/T18380.2-2001

(IEC60332-2-25:1989)

25<D≤50120
50<D≤75240
D>75480

B The bundle flame-retardant

Code


Volume ofspecimenno-metallic

material(L/m)


For fire timeindex



Compliance

index


Test method

ZA


ZB


ZC


ZD

7


3.5


1.5


0.5

40


40


20


20


1.Specimen carbonation is far from theedge of nozzle as 2.5m


2.The flaming time is no longer than 1hafter fired

GB/T18380.3-2001(IEC60332-3:1992)(IEC60332-3-25:2000)



Online Message

Message

Leave your question and we will respond promptly to get back to you

  • Telephone

    +86-152-6220-7107

  • Mailbox

    jinxincable@yzjxdl.com

  • Previous:XPLE insulated Control Cable2023-08-14

    Recently Viewed:

    CONTACT US

    Tell:+86-152-6220-7107

    Email: jinxincable@yzjxdl.com

    Website: www.yzjxdl.com

    FaceBook: JX Cable

    whatsapp: http://wa.me/8615262207107


    Copyright © 2024 Yangzhou Jinxin Cable Co., Ltd All Rights Reserved Technical Support: Ximi network